300
KYN28-12(24) switchgear
Category:
Email:
General description:
Product Description
KYN28-12(24) Metal-clad Switchgear
—— 10 kV / 20 kV dual-voltage platform, core equipment for indoor power distribution and power reception
I. Product Overview
KYN28-12(24) is an indoor metal-clad, withdrawable (center-mounted) high-voltage switchgear designed according to GB 3906-2006 and IEC 62271-200. It is a three-phase 50 Hz switchgear with a rated voltage of 12 kV (expandable to 24 kV), used for power generation plants, substations, industrial and mining enterprises, and large motor power distribution and reception. It has complete "five-prevention" interlocking functions.
II. Technical Parameters
Item |
12 kV rating |
24 kV rating |
Rated Voltage Ur |
12 kV |
24 kV |
Rated Current Ir |
630 – 4000 A |
630 – 3150 A |
Rated Short-Circuit Breaking Current Ik |
25 / 31.5 / 40 / 50 kA |
25 / 31.5 / 40 kA |
Rated Short-Time Withstand Current Icw (4 s) |
25 / 31.5 / 40 kA |
25 / 31.5 / 40 kA |
Rated Peak Withstand Current Ip |
63 / 80 / 100 / 125 kA |
63 / 80 / 100 kA |
Power Frequency Withstand Voltage (1 min) |
42 kV |
50 kV |
Lightning Impulse Withstand Voltage |
75 kV |
125 kV |
Protection Level |
Enclosure IP4X, Compartment IP2X |
Same as above |
Internal Arc Classification |
IAC AFLR 31.5 kA / 1 s |
Same as above |
Mechanical Life |
≥ 20,000 times |
≥ 20,000 times |
Optional Circuit Breaker |
VS1(ZN63), VD4, VK series |
Same as above |
III. Structural Features
1. The cabinet is made of imported aluminum-zinc coated steel plate with multiple bending and bolting, ensuring high cabinet strength, light weight, and corrosion resistance.
2. Center-mounted trolley: plug-in interchangeable, with mechanical interlocking in "operation-test-isolation" three positions, convenient for maintenance.
3. Four independent compartments: circuit breaker compartment, busbar compartment, cable compartment, and low-voltage instrument compartment. Independent pressure relief channels ensure personal safety in case of faults.
4. The cable compartment has ample space and can connect multiple 1×240 mm² XLPE cables; cable entry/exit can be any combination of top/bottom.
5. Optional heater, lighting, and temperature and humidity controller to prevent condensation and salt spray corrosion.
IV. Typical Dimensions (Width × Depth × Height)
Rated Current |
12 kV Cabinet |
24 kV Cabinet |
≤ 1250 A |
800 × 1500 × 2300 mm |
800 × 1650 × 2300 mm |
1600 – 3150 A |
1000 × 1500 × 2300 mm |
1000 × 1750 × 2300 mm |
V. Application Scenarios
• Urban distribution network substations, ring networks
• Power plant auxiliary power, small and medium-sized generator outlets
• Substations for metro, data centers, and hospitals (10 kV / 20 kV)
• On-site power distribution and starting of high-voltage motors in industrial and mining enterprises
VI. Implementation Standards
GB 3906-2006, IEC 62271-200, DL/T 404. Passed the type test of the National High-Voltage Electrical Apparatus Quality Supervision and Inspection Center, with LSC2 loss of operating continuity category.
VII. Ordering Information
Please provide: rated voltage, rated current, short-circuit breaking current, input/output method, circuit breaker brand, and secondary schematic diagram. Supports wall-mounted or back-to-back arrangement, and can be equipped with arc protection, wireless temperature measurement, and intelligent online monitoring.
Key word: Photovoltaic | Semiconductor | Silicon Carbide | Sapphire | Magnetic Materials | Silicon Wafer Cutting Service
Relevant Products
Contact Us
*Note: Please be sure to fill in the information accurately, and keep the communication unblocked, we will get in touch with you as soon as possible
*Note: be sure the information is filled accurately and the communication is clear, and we will get in touch with you as soon as possible