An integrated solution of "dual power supply at the end + fire linkage" specially designed for smoke exhaust fans
I. Core Functions
1. Dual Power Supply Switching
• PC-level ATS, switching time ≤ 50 ms, supporting self-starting and self-recovery, and mutual backup logic;
• Main/backup power supply, closing, and fault, four independent indicator lights for clear visibility.
2. Fan Control
• Three modes: manual/automatic/remote, manual priority;
• In automatic mode, it can receive 24V active or passive fire linkage signals, start the fan and illuminate the red "start" indicator light;
• 280 ℃ fire damper fuse signal forces shutdown and feedback to the fire control room.
3. Multiple Protections
• Overcurrent, short circuit, phase loss, phase error, overvoltage, undervoltage, overload 150% 1 min protection action;
• In case of failure, the audible and visual alarm will continuously alert at 90 dB until manual reset.
4. Signal Feedback
• Standard configuration of 10 sets of passive contacts: fan operation, fan fault, manual/automatic status, power status, fire damper action;
• Reserved RS-485 interface, supporting Modbus-RTU or fire two-bus access to FAS/BA system.
II. Technical Parameters
Item |
Value |
Rated Operating Voltage |
AC 380 V three-phase four-wire |
Rated Power |
5.5 – 75 kW (expandable to 110 kW) |
Control Voltage |
DC 24 V (linkage) |
Protection Level |
IP55 (outdoor IP65 available) |
Short-time Withstand |
15 kA/1 s |
Ambient Temperature |
-5 ℃ ~ +40 ℃ |
Relative Humidity |
≤ 90 % (+40 ℃) |
Altitude |
≤ 2000 m |
III. Structure and Installation
• 1.5 mm cold-rolled steel electrostatic spraying, front door viewing window + three-point lock, preventing unauthorized operation;
• Input/output method: top/bottom double knock-out holes, cables directly enter and exit;
• Standard wall-mounted or floor-standing installation, dimensions (width × height × depth)
– 5.5–22 kW:500 × 650 × 250 mm
– 30–75 kW:600 × 800 × 300 mm
• Ground copper bar ≥ 25 × 3 mm, grounding resistance ≤ 0.1 Ω.
IV. Implementation Standards
GB 16806-2006 "Fire Linkage Control System"
GB 51251-2017 "Technical Standard for Building Smoke Exhaust System"
GB/T 21208-2020 "Low-voltage switchgear and controlgear Power supply and control equipment for fire equipment"
With CCCF mandatory certification and type test report.
V. Ordering Information
Please provide: fan power, ATS current rating, installation method, whether communication interface and fire linkage contact number are required. OEM color, Logo and special size customization are supported.
Key word: Photovoltaic | Semiconductor | Silicon Carbide | Sapphire | Magnetic Materials | Silicon Wafer Cutting Service
Relevant Products
Contact Us
*Note: Please be sure to fill in the information accurately, and keep the communication unblocked, we will get in touch with you as soon as possible
*Note: be sure the information is filled accurately and the communication is clear, and we will get in touch with you as soon as possible